Welcome: WarmCloud (Nantong) Energy Technology Co., Ltd.
Language: Chinese ∷  English

Commercial and Industrial Large-Scale Energy Storage System

  • C&I Large-Scale ESS
  • C&I Large-Scale ESS
C&I Large-Scale ESSC&I Large-Scale ESS

C&I Large-Scale ESS

  • Product description: WarmCloud Commercial and Industrial Large-Scale Energy Storage System is specifically designed for industrial and commercial users, consisting of high-capacity battery systems used to store electrical
  • INQUIRY

Product Advantages:

1.High Energy Density Featuring ultra-high volumetric energy density with dual-chamber parallel connection, it saves floor space.

2.Ultra-High Safety Equipped with cell-level temperature monitoring and thermal insulation to prevent fire spread at the cell level, pack-level immersion suppression, full flooding gas extinguishing systems, and complete compartment fire water sprinklers for enhanced safety.

3.Standardization Modular design ensures rational layout and easy maintenance; it comes in a standard 20-foot container size, facilitating loading, unloading, transportation, and installation.

4.Intelligent Temperature Control Technology Modular adjustable pipelines achieve high uniform temperature performance of Battery Management System (BMS) and liquid cooling interlock control for efficient energy saving.

Model

ESD1331-05P5015

ESD1280-05P5068

Electrical Parameters

Cell capacity

314Ah

330Ah

Nominal energy

5015.9kWh

5068.8kWh

Nominal voltage

1331.2V

1280V

Use voltage range recommended

1164.8V-1497.6V

1120V-1440V

Maximum Charge / Discharge rate

0.5P@25℃

0.5P@25℃

Maximum Charging power

2507.9kW(0.5P)

2534.4kW(0.5P)

Environmental Parameters

Storage Temperature range

-30℃~60℃

Operating Temperature range

-30℃~45℃

Operating Humidity range

≤95%

Altitude

<3000m

Coefficient parameters

Levels of protection

IP55

Heat Management

Liquid cooling

Communication Mode

CAN,RS485,Ethernet

Protocol

Modbus-TCP/P

Fire Extinguisher system

Pack-level Immersion Fire Suppression + Total Flooding Gas Fire Extinguishing + Water-based Fire Suppression

Criterion *

(Ongoing)

GB/T36276,UL1973,UL9540,UL9540A,

UN38.3,UN3536,IEC62477,IEC60730,

IEC61000,IEC62619,NFPA855 Compliant

Dimensions (W * D * H)

6058mm*2438mm*2896 mm

Weight

≈43t


Model

ESD1126

-05P2703

ESD1267

-05P3421

ESD1280

-05P4608

Electrical parameters

Cell capacity

100Ah

300Ah

300Ah

Nominal energy

2703.3kWh

3421.4kWh

4608kWh

Nominal voltage

1126V

1267V

1280V

Use voltage range recommended

985.6V~1267.2V

1108.8V-1425.6V

1120~1440V

Maximum Charge / discharge rate

0.5 P@25℃

0.5P@25℃

0.5P@25℃

Maximum Charging power

1351.6kW(0.5P)

1710.7kW(0.5P)

2304kW(0.5P)

Environmental parameter

Operating temperature range

-30-45℃

Operating Humidity range

0-95%

Levels of protection

IP54

Cooling-down method

Air cooling

Liquid cooling

Liquid cooling

Fire Suppression System

Sevofluoropropane / Perfluorohexanone

Altitude

<3000m

Communication Mode

CAN,RS485,Ethernet

Criterion

UL1973,UL9540A,IEC62619,UN38.3,

IEC62477,IEC61000IEC60730,IEC62933, GB/T 36276

UN38.3*,

UL1973*,

UL9540A,

GB/T 36276

Configuration Parameters

Dimensions

(W * D * H)

6058mm*2438mm*2896mm

Weight

≈32t

≈37t

≈43t